Circuit Breaker Size Calculator

Circuit Breaker Size Calculator

Estimate breaker size from watts and volts, apply the 125% continuous-load rule, round to common standard sizes, and compare the result with simple wire ampacity references.

1Load presets

Choose a real home load preset, then adjust the values for the actual equipment nameplate and circuit plan.

2Circuit inputs

Single phase uses amps = watts / volts.
Use the load voltage, such as 120, 208, or 240 V.
Use nameplate watts or volts multiplied by amps.
Continuous loads are expected to run 3 hours or more.
Leave at 1.00 for resistive loads or unknown home loads.
Optional planning margin after continuous-load sizing.
Final conductor sizing depends on wiring method and terminals.
Use a practical cap for the panel, feeder, or equipment.
Code-check note: This calculator is an estimating aid, not an approval document. Verify the final breaker, conductor, insulation temperature, terminal rating, equipment listing, local amendments, neutral loading, motor rules, and permitting requirements with the current electrical code and a qualified electrician.
W/V
Single-phase amps
125%
Continuous load
80%
Continuous guide
NEC
Check locally
Recommended standard breaker
20 A
next standard size
Sizing load after rules
15.6 A
continuous + noncontinuous
Wire ampacity reference
12 AWG Cu
60°C reference column
80% continuous load guide
16.0 A
max continuous on selected breaker

3Wire ampacity reference

Reference values below are simplified 60°C conductor examples for common home planning. They do not replace code tables, correction factors, or equipment instructions.

14 Cu
15 amp branch circuit
12 Cu
20 amp branch circuit
10 Cu
30 amp branch circuit
8 Cu
40 amp branch circuit
6 Cu
55 amp reference
4 Cu
70 amp reference
8 Al
30 amp reference
6 Al
40 amp reference

4Reference tables

Standard breaker 80% continuous guide Typical single-phase watts at 120 V Typical single-phase watts at 240 V
15 A12 A1,440 W2,880 W
20 A16 A1,920 W3,840 W
30 A24 A2,880 W5,760 W
40 A32 A3,840 W7,680 W
50 A40 A4,800 W9,600 W
60 A48 A5,760 W11,520 W
AWG or kcmil Copper 60°C Aluminum 60°C Planning note
14 AWG15 ANot typicalLighting branch circuits
12 AWG20 A15 A referenceGeneral receptacles
10 AWG30 A25 A referenceSmall appliance loads
8 AWG40 A30 A referenceLarge home loads
6 AWG55 A40 A referenceEquipment circuits
4 AWG70 A55 A referenceFeeder planning
Load preset Watts and volts Continuous portion Likely breaker range
Bedroom lighting600 W at 120 V100%15 A minimum common size
Portable heater1500 W at 120 V100%20 A when continuous
Microwave outlet1800 W at 120 V0%15 to 20 A by nameplate
Water heater4500 W at 240 V100%25 to 30 A range
EV outlet9600 W at 240 V100%50 A for 40 A continuous
3-phase shop load12000 W at 208 V70%45 to 50 A range

5Practical sizing tips

Use the equipment nameplate. Breaker sizing starts with the actual listed watts or amps, then applies continuous-load and equipment-specific rules where required.
Do the code check before installing. Motors, HVAC equipment, EV charging, kitchen appliances, multiwire branch circuits, conductor bundling, ambient temperature, and panel limitations can change the final answer.

Okay so you’re remodeling something and suddenly the breaker trips. Why? Because the tool you were using require more amps than what the circuit will allow. There is a reason why breakers should of been sized properly. It’s not just theory; it’s safety.

So you take a look at the wattage rating, divide by voltage, and there’s your amp. Now you’ll round up to the next closest breaker size. The problem is solved, right? That approach ignores thermal reality of the wiring inside your walls. That doesn’t account for effects of heat on copper wire in your walls. Current has a limit. Pushing too much current into 14-gauge wire will cause insulation to degrade. There won’t be a trip, there will be heat. And heat leads to fire.

Why Wire and Breaker Size Matters

We want the breaker to match weakest link in our system. In most cases, that’s the wire.

But what about continuous loads? If you turn something on for three hours or more, it’s a continuous load. But if you turn it on and off every few minutes for ten minutes total, it’s not a continuous load. Continuous loads are considered more dangerous; they create steady heat where spikes don’t, so the code call for sizing the breaker with 125% of the load if it will be running for at least three hours continuously. That additional capacity is a safety buffer.

The calculator above do that math for you. It automatically assumes you’ll want 125% so you don’t have to think about the fraction. It then rounds up to the nearest standard size. This means you won’t need to install a custom breaker, which no one carries.

This section covers wire gauge and breaker size. Why does this matter? For example, you’ll typically find 15-amp breaker used for lighting circuits (which is rated for use with 14-gauge copper wire). Never replace that 15-amp breaker with a 20-amp one, even if you suspect there may be frequent nuisance trips. That’s no longer providing safety protection. In the event of a short, the wire would melt without tripping the breaker. Remember: It’s the wire that determines the breaker, and not vice versa.

You can refer to the table on the page for some examples: 12-gauge wire can handle 20 amps; 10-gauge wire can handle 30 amps. These figures is based off lots of research and testing over many years using different types of insulating material at various temperatures.

Homeowners often forget the 80% rule when it comes to constant loads and regular breakers. Continuous loads must be kept below 80% of the amp rating of the breaker. For example, a 20-amp breaker is rated for 16 amps of continuous load. Why? Because a breaker is a thermal device. It trips by heating up. The longer you run a circuit at max output, the more likely that breaker will overheat and fail prematurely. Keeping continuous loads under 80% keeps the breaker within safe operating temperature. For electrical panels, this is important for their lifespan.

Also note that most household outlets are single-phase, but many large appliances like electric ranges or dryers uses 240 volts. Single-phase is most common throughout the house. Many large appliance (e.g., electric range) require 240 volts. That impacts how you calculate the amperage. If you have a high-voltage circuit (240 vs. 120), then you’ll get fewer amps for the same amount of power. Fewer amps means smaller wire and smaller breaker. High-voltage circuits is good for heavy machinery; but they can be lethal if wired incorrectly. Always read the voltage required off the piece of equipment‘s nameplate. If it says 240 volts but you assume 120 volts instead, you just doubled your amperage estimate. That creates some pretty major size mistakes.

The tool isn’t a permit; it’s an aid for planning. It explains how voltage, power and protection relate. It indicates whether what you plan is reasonable or not. But local codes differ. Attic heat degrades wire capacity. Heat builds when cables are bundled. A qualified electrician check these and other variables before any wire installation.

The calculator is meant as a conversation starter with your contractor. It demonstrates that you’ve done your homework. You’ll be able to ask the right questions.

You want a system that stays cool under pressure. Only then will the sizing work, the walls remain cool and the lights stay on.

Circuit Breaker Size Calculator

Leave a Comment